Climate Talk Fault Code Transmitted message Dealer error message Possible Causes Corrective Actions Alarm Status Unit Type Consumer error message
               
               
11 RUN SYS TEST System Test required for start up •Incomplete SYSTEM TEST.
•SYSTEM TEST is running.
•MESSAGE ONLY. Critical AC & HP System error
12 OD CTRL Fail 1 General memory error •High electrical noise.
•Faulty control board.
•Replace control board if necessary. Critical AC & HP System error
13[1] HI PRESSURE C Experiencing frequent high pressure faults •Blocked/restricted condenser coil and /or lines.
•Stop valve not completely open.
•Overcharged.
•Outdoor fan not running.
•High pressure switch (HPS) inoperable.
•Faulty indoor EEV or TXV.
•Faulty indoor EEV coil.
•Faulty control board.
•DV**PEC air handler is connected with DX20VC0**1AA or AB.
•Check and clean condenser coil and/or lines.
•Check the opening of stop valve, should be fully open; Repair/replace if needed.
•Check refrigerant charge level; Adjust if needed.
•Check outdoor fan motor & wiring; Repair/replace if needed.
•Check indoor EEV or TXV; Replace if needed.
•Check indoor EEV coil; Replace if needed.
•Replace control board if necessary.
•Replace indoor unit with TXV applicable indoor unit.
Critical AC & HP Pressure error
14[2] HI PRESSURE M Experiencing frequent high pressure faults but acceptable to run •Blocked/restricted condenser coil and/or lines.
•Stop valve not completely open.
•Overcharged.
•Outdoor fan not running.
•High pressure switch (HPS) inoperable.
•Faulty indoor EEV or TXV.
•Faulty indoor EEV coil.
•Faulty control board.
•DV**PEC air handler is connected with an incompatible model.
•Check and clean condenser coil and/or lines.
•Check the opening of stop valve, should be fully open; Repair/replace if needed.
•Check refrigerant charge level; Adjust if needed.
•Check outdoor fan motor & wiring; Repair/replace if needed.
•Check indoor EEV or TXV; Replace if needed.
•Check indoor EEV coil; Replace if needed.
•Replace control board if necessary.
•Check high pressure switch; Replace if necessary.
•Replace indoor unit with TXV applicable indoor unit.
minor AC & HP Pressure error
15 LOW PRESSURE C Frequent low pressure faults •Stop valve not completely open.
•Restriction in refrigerant lines.
•Low refrigerant charge.
•Refrigerant leak.
•Low pressure sensor inoperable or not properly connected.
•Indoor fan motor not functioning correctly.
•Faulty indoor EEV or TXV.
•Faulty indoor EEV coil.
•Faulty Control board
•DV**PEC air handler is connected with an incompatible model.
•Check the opening of stop valve, should be fully open; Repair/replace if needed.
•Check for restrictions in refrigerant line; Repair/replace if needed.
•Check refrigerant charge level; Adjust if needed.
•Test for system leaks using leak test procedure.
•Check the connection to low pressure sensor; Repair/replace if needed.
•Check indoor EEV or TXV; Replace if needed.
•Check indoor EEV coil; Replace if needed.
•Check indoor blower motor & wiring; Repair/replace if needed.
•Replace control board if necessary.
•Replace indoor unit with TXV applicable indoor unit.
Critical AC & HP Pressure error
16 LOW PRESSURE M Frequent low pressure faults •Stop valve not completely open.
•Restriction in refrigerant lines.
•Low refrigerant charge.
•Refrigerant leak.
•Low pressure sensor inoperable or not properly connected.
•Indoor fan motor not functioning correctly.
•Faulty indoor EEV or TXV.
•Faulty indoor EEV coil.
•Faulty Control board
•DV**PEC air handler is connected with an incompatible model.
•Check the opening of stop valve, should be fully open; Repair/replace if needed.
•Check for restrictions in refrigerant line; Repair/replace if needed.
•Check refrigerant charge level; Adjust if needed.
•Test for system leaks using leak test procedure.
•Check the connection to low pressure sensor; Repair/replace if needed.
•Check indoor EEV or TXV; Replace if needed.
•Check indoor EEV coil; Replace if needed.
•Check indoor blower motor & wiring; Repair/replace if needed.
•Replace control board if necessary.
•Replace indoor unit with TXV applicable indoor unit.
minor AC & HP Pressure error
17 COMPRESSOR FAIL Frequent compressor faults •Stop valve not completely open.
•The compressor wire has lost phase.
•Compressor motor failure.
•Check the opening of stop valve, should be fully open; Repair/replace if needed.
•Check the wire between control board and compressor.
•Inspect compressor motor for proper function; Replace if necessary.
Critical AC & HP System error
18   Outdoor control board error •Outdoor fan motor not connected properly.
•Faulty control board.
•Noise.
•Check wiring from outdoor fan motor to control board; Repair if needed.
•Replace control board if necessary.
Critical AC & HP System error
19   Outdoor unit PCB or fan failure error •Obstruction in fan rotation.
•Outdoor fan motor not connected properly.
•Outdoor fan not running.
•Faulty control board.
•Noise.
•Check and clean grille of any debris.
•Check wiring from outdoor fan motor to control board; Repair if needed.
•Check outdoor fan motor & wiring; Repair/replace as needed.
•Replace control board if necessary.
Critical AC & HP System error
20   EEV coil is not connected •Outdoor EEV coil is not connected.
•Faulty outdoor EEV coil.
•Check outdoor EEV coil connection; Repair/replace as needed. Critical AC & HP System error
21[3] EEV CTRL FAIL Experiencing frequent low discharge superheat faults •Thermistors inoperable or improperly connected.
•Faulty indoor EEV coil.
•Faulty indoor EEV or TXV.
•Faulty outdoor EEV coil.
•Faulty outdoor EEV.
•Overcharged.
•Faulty pressure sensor.
•Faulty control board.
•DV**PEC air handler is connected with an incompatible model.
•Check the connection to thermistors; Repair/replace if needed.
•Check indoor EEV coil; Repair/replace if needed.
•Check indoor EEV or TXV; Repair/replace if needed.
•Check outdoor EEV coil; Repair/replace if needed.
•Check outdoor EEV; Repair/replace if needed.
•Check refrigerant charge level; Adjust if needed.
•Check pressure sensor; Repair/replace if needed.
•Replace control board if necessary.
•Replace indoor unit with TXV applicable indoor unit.
Critical AC & HP System error
22   Hi discharge temperature error •Discharge thermistor inoperable or improperly connected.
•Discharge thermistor is set to incorrect position or off.
•Low refrigerant charge.
•Overcharged.
•Faulty Compressor.
•Check discharge thermistor resistance and connections; Repair/replace as needed.
•Check discharge thermistor position.
•Check refrigerant charge level; Adjust if needed.
•Check the compressor; Repair/replace if needed.
Critical AC & HP Sensor error
23   discharge temperature sensor failure •Discharge thermistor inoperable or improperly connected. •Check discharge thermistor resistance and connections; Repair/replace as needed. Critical AC & HP Sensor error
24 HPS OPEN High pressure switch is open •High pressure switch (HPS) inoperable. •Check resistance on HPS to verify operation; Replace if needed. Critical AC & HP Pressure error
25   Outdoor  temperature sensor error •Faulty or disconnected  outdoor thermistor sensor. •Inspect and test sensor; Replace sensor if needed. Critical AC & HP Sensor error
26[4] PRESSURE SENSOR Pressure sensor not reacting properly •Low pressure sensor inoperable or not properly connected. •Check the connection to low pressure sensor; Repair/replace as needed. Critical AC & HP Pressure error
27   Outdoor defrost sensor error •Outdoor defrost thermistor inoperable or not properly connected. •Check the connection to outdoor defrost thermistor; Repair as needed. Critical AC & HP Sensor error
28   Outdoor coil temperature sensor error •Outdoor coil thermistor inoperable or not properly connected. •Check the connection to outdoor coil thermistor; Repair/replace if needed. Critical AC & HP Sensor error
29   Liquid temperature sensor error •Liquid thermistor inoperable or not properly connected. •Check the connection to liquid thermistor; Repair/replace if needed. Critical AC & HP Sensor error
30[5] OD CTRL FAIL 3 Control board may need to be replaced •Wiring to control board disconnected.
•Faulty control board.
•Noise.
•Check wiring to control board; Repair as needed.
•Replace control board if necessary.
Critical AC & HP Communication error
31   High current leak •Improper ground.
•Faulty compressor.
•Check ground screws/lugs and wiring; Repair/replace if needed.
•Check the compressor. Repair/replace if needed.
Critical AC & HP Safety error
32   Outdoor unit control board high temperature fault •Ambient air conditions too high.
•Cooling bracket screw(s) missing or not properly fastened (2-4 ton only).
•No or poor thermal grease coating between cooling plumbing and cooling bracket on control board (2-4 ton only).
•Outdoor fan low speed (5 ton only).
•No flow or limited flow through control board cooling circuit (potential restriction in line or low refrigerant) (2-4 ton only).
•Stop valve not completely open (2-4 ton only).
•Cycle power; retry during usable ambient temperature range.
•Verify cooling bracket screws in place and secure; Secure fasteners as needed (2-4 ton only).
•Check thermal grease inside cooling bracket on control board; Apply additional grease as needed.
•Check outdoor fan motor & wiring; Repair/replace if needed (5 ton only).
•Check for restriction in line.
•Check refrigerant charge level; Adjust if needed (2-4 ton only).
•Check the opening of stop valve, should be fully open; Repair/replace if needed (2-4 ton only).
Critical AC & HP Sensor error
33   Outdoor unit control board high temperature fault but acceptable to run •Ambient air conditions too high.
•Cooling bracket screw(s) missing or not properly fastened (2-4 ton only).
•No or poor thermal grease coating between cooling plumbing and cooling bracket on control board (2-4 ton only).
•Outdoor fan low speed (5 ton only).
•No flow or limited flow through control board cooling circuit (potential restriction in line or low refrigerant) (2-4 ton only).
•Stop valve not completely open (2-4 ton only).
•Cycle power; retry during usable ambient temperature range.
•Verify cooling bracket screws in place and secure; Secure fasteners as needed (2-4 ton only).
•Check thermal grease inside cooling bracket on control board; Apply additional grease as needed.
•Check outdoor fan motor & wiring; Repair/replace if needed (5 ton only).
•Check for restriction in line.
•Check refrigerant charge level; Adjust if needed (2-4 ton only).
•Check the opening of stop valve, it should be fully open; Repair/replace if needed (2-4 ton only).
minor AC & HP Sensor error
34   Outdoor unit PCB detected a possible short circuit •Current spike in supply.
•Stop valve not completely open.
•The compressor wire has lost phase.
•Faulty control board.
•Faulty compressor.
•Check power supply for inrush current during start up or steady state operation.
•Check the opening of stop valve, should be fully open; Repair/replace if needed.
•Check the wire between control board and compressor.
•Replace control board if necessary.
•Check the compressor; Repair/replace if needed.
Critical AC & HP Safety error
35   Outdoor unit PCB detected a high current condition •Short circuit condition.
•Stop valve not completely open.
•Overcharged.
•Faulty control board.
•Faulty compressor.
•Check installation clearances.
•Check the opening of stop valve, should be fully open; Repair/replace if needed.
•Check refrigerant charge level; Adjust if needed.
•Replace control board if necessary.
•Check the compressor; Repair/replace if needed.
Critical AC & HP Safety error
36 STARTUP ERROR Startup procedure error •Blocked/Restricted condenser coil and/or lines.
•The compressor wire has lost phase.
•Inconsistent compressor load.
•Faulty control board.
•Check and clean condenser coil and/or lines.
•Check the wiring between control board and compressor.
•Replace control board if necessary.
Critical AC & HP System error
37 OD CTRL FAIL 4 Control board error •Outdoor fan motor not connected properly.
•Faulty control board.
•Check wiring from outdoor fan motor to control board; Repair if needed.
•Replace control board if necessary.
Critical AC & HP System error
38   Compressor voltage error •High or low voltage from supply.
•The compressor wire has lost phase.
•Faulty control board.
•Correct low/high line voltage condition; Contact local utility if needed.
•Check the wire between control board and compressor.
•Replace control board if necessary.
Critical AC & HP System error
39[6] OD CTRL FAIL 5 Control board may need to be replaced •Thermistors inoperable or improperly connected.
•Faulty control board.
•Check the connection to thermistors; Repair/replace if needed.
•Replace control board if necessary.
Critical AC & HP System error
40[7] COMP MISMATCH Compressor requirement is different than the capability •Memory card not correct.
•Control board mismatch.
•Check memory card data vs. air conditioner model.
•Verify control board size vs. air conditioner model; Replace control board if necessary.
Critical AC & HP System error
41 LOW REFRIGERANT Low refrigerant condition error •Refrigerant leak.
•Low refrigerant charge.
•Thermistors inoperable or not properly connected.
•Test for system leaks using leak test procedure.
•Check refrigerant charge level; Adjust if needed.
•Check the connection to the thermistor; Repair/replace if needed.
Critical AC & HP System error
42[8] LOW LINE VOLT Low power supply voltage condition detected •Low line voltage supply. •Check circuit breakers and fuses; Replace if needed.
•Verify unit is connected to power supply as specified on rating plate.
•Correct low line voltage condition; Contact local utility if needed.
Critical AC & HP Safety error
43[9] HIGH LINE VOLT High power supply voltage condition detected •High line voltage supply. •Verify unit is connected to power supply as specified on rating plate.
•Correct high line voltage condition; Contact local utility if needed.
Critical AC & HP Safety error
44   Recommended outdoor operational temperature is out of range •Ambient air conditions too high or low. •Cycle power; retry during usable ambient temperature range. minor AC & HP System error
45 NO COOLING TEST Cooling mode test error •Heat provided by secondary heating source. •Turn off heater using thermostat before running AHRI mode. Critical AC & HP System error
46[10] NO HEATING TEST Unable to start heating mode test.  Set thermostat to off position •Heat provided by secondary heating source. •Turn off heater using thermostat before running AHRI mode. Critical AC & HP System error
47[11] NO SYS VER TEST Unable to start system verification test.  Set thermostat to off position •Heat provided by secondary heating source. •Turn off heater using thermostat before operation. Critical AC & HP System error
48[12] NO PUMP DOWN Unable to enter pump down mode.  Set thermostat to off position •Heat provided by secondary heating source. •Turn off heater using thermostat before operation. Critical AC & HP System error
49[13] NO CHARGE MODE Unable to enter charging mode.  Set thermostat to off position •Heat provided by secondary heating source. •Turn off heater using thermostat before operation. Critical AC & HP System error
50[14] LINE VOLT CTRL Voltage issue on the control board.  See manual for troubleshooting info •High or low voltage from supply.
•Faulty control board.
•Correct low/high line voltage condition; Contact local utility if needed.
•Replace control board if necessary.
Critical AC & HP Safety error
51[15] OD COMM ERROR Potential communication issues have been detected by the outdoor control board •Communication wiring disconnected. •Check communication wiring; Repair as needed. Critical AC & HP Communication error
52[16] COMP FAIL MINOR Experiencing frequent compressor faults but acceptable to run •Stop valve not completely open.
•The compressor wire has lost phase.
•Compressor motor failure.
•Check the opening of stop valve, should be fully open; Repair/replace if needed.
•Check the wire between control board and compressor.
•Inspect compressor motor for proper function; Replace if necessary.
minor AC & HP System error
53 PCB OR FAN MIN Frequent outdoor faults •Obstruction in fan rotation.
•Outdoor fan motor not connected properly.
•Outdoor fan not running.
•Faulty control board.
•Noise.
•Check and clean grille of any debris.
•Check wiring from outdoor fan motor to control board; Repair if needed.
•Check outdoor fan motor & wiring; Repair/replace as needed.
•Replace control board if necessary.
minor AC & HP System error
54 EEV MINOR Experiencing frequent low discharge superheat faults but acceptable to run •Thermistors inoperable or improperly connected.
•Faulty indoor EEV or TXV or indoor EEV coil.
•Faulty control board.
•DV**PEC air handler is connected with an incompatible model.
•Check the connection to thermistors; Repair/replace if needed.
•Check indoor EEV or TXV; Replace if needed.
•Check indoor coil; Replace if needed.
•Replace control board if necessary.
•Replace indoor unit with TXV applicable indoor unit.
minor AC & HP System error
55   Frequent low discharge superheat faults but acceptable to run •Discharge thermistor inoperable or improperly connected.
•Discharge thermistor is set to incorrect position or off.
•Low refrigerant charge.
•Overcharged.
•Faulty Compressor.
•Check discharge thermistor resistance and connections; Repair/replace as needed.
•Check discharge thermistor position.
•Check refrigerant charge level; Adjust if needed.
•Check the compressor; Repair/replace if needed.
minor AC & HP System error
56   Suction temperature sensor failure •Suction thermistor inoperable or not properly connected •Check the connection to suction thermistor; Repair/replace if needed
•Check for obstruction inside duct work
Critical AC & HP Sensor error
57   Control is sensing sweating on the cooling loop •Refrigerant leak.
•Low refrigerant charge.
•Thermistors inoperable or not properly connected.
•Faulty indoor EEV or indoor EEV coil.
•Test for system leaks using leak test procedure.
•Check refrigerant charge level; Adjust if needed.
•Check the connection to the thermistor; Repair/replace if needed.
•Chesk indoor EEV; Replace if needed.
•Check indoor EEV coil; Replace if needed.
minor AC & HP System error
58   Compressor overload protection sensor is open •Overload protection (OL) sensor is inoperable  •Check resistance on OL sensor to verify operation; Replace if needed.
•Check OL sensor position on compressor body.
Critical AC & HP System error
59   Equipment is experiencing reversing valve faults •Faulty reversing valve body or coil.
•Low refrigerant charge.
•Faulty pressor sensor.
•Faulty control board.
•Check reversing valve body or coil; Replace if needed
•Check refrigerant charge level; Adjust if needed.
•Check pressor sensor; Replace if needed.
•Replace control board if necessary.
Critical AC & HP System error
60   The heat pump is recovering from a sudden loss of power •While heating with heat pump there was a sudden loss of power •Check for proper voltage to HP
•If immediate heat is required run in cool mode for 5 minutes then switch back to heat mode.
minor AC & HP System error
60   The heat pump is recovering from a sudden loss of power •While in heat mode there was a sudden loss of power •Check for proper voltage to HP
•If immediate heat is required run in cool mode for 5 minutes then switch back to heat mode.
Critical AC & HP System error

[1]
Roff, Jeff D.:
experiencing frequent high pressure faults
[2]
Roff, Jeff D.:
Same as 13.  Continued operation is acceptable. There may be a equipment problem
[3]
Roff, Jeff D.:
indicates equipment is experiencing frequent low discharge superheat faults
[4]
Roff, Jeff D.:
The control determines that the pressure sensor is not reacting properly
[5]
Roff, Jeff D.:
indicates the control board may need to be replaced
[6]
Roff, Jeff D.:
Indicates the control board may need to be replaced
[7]
Roff, Jeff D.:
Control determines that its compressor requirement is different than the capability
[8]
Roff, Jeff D.:
Control detects a low power supply voltage condition
[9]
Roff, Jeff D.:
Control detects a high power supply voltage condition
[10]
Roff, Jeff D.:
Unable to start heating mode test.  Set thermostat to off position
[11]
Roff, Jeff D.:
unable to start system verification test.  Set thermostat to off position
[12]
Roff, Jeff D.:
unable to enter the pump down mode.  Set thermostat to off position
[13]
Roff, Jeff D.:
unable to enter charging mode.  Set thermostat to off position
[14]
Roff, Jeff D.:
there is a voltage issue on the control board.  See manual for troubleshooting info
[15]
Roff, Jeff D.:
potential communication issues have been detected by the outdoor control board
[16]
Roff, Jeff D.:
equipment is experiencing frequent compressor faults.  Cnt'd operation okay