Climate Talk Fault Code | Transmitted message | Dealer error message | Possible Causes | Corrective Actions | Alarm Status | Unit Type | Consumer error message |
01 | LOW SIDE FAULT | Low side fault | •Low
refrigerant charge. •Restriction in liquid line. •Indoor blower motor failure. •Indoor thermostat set extremely low. |
•Verify
refrigerant charge; adjust as needed. •Check for restricted liquid line; repair/replace as needed. •Check indoor blower motor; repair/replace as needed. •Check indoor thermostat setting. |
minor | 2-Stage AC | Pressure error |
01 | LPS LOCKOUT | Low pressure cut out trip/lockout(3 trips) | •Low
refrigerant charge. •Restriction in liquid line. •Indoor blower motor failure. •Indoor thermostat set extremely low. |
•Verify
refrigerant charge; adjust as needed. •Check for restricted liquid line; repair/replace as needed. •Check indoor blower motor; repair/replace as needed. •Check low pressure switch; repair/replace as needed. •Check indoor thermostat setting. |
Critical | 2-Stage AC | Pressure error |
02 | HPS OPEN | High side fault | •Blocked
condenser coil. •Outdoor fan not running. |
•Check
and clean condenser coil. •Check outdoor fan motor; repair/replace as needed. •Check outdoor fan motor wiring; repair/replace as needed. •Check outdoor fan motor capacitor; repair/replace as needed. |
minor | 2-Stage AC | Pressure error |
02 | HPS LOCKOUT | High pressure cut out/lockout(3 trips) | •Blocked
condenser coil. •Outdoor fan not running. |
•Check
and clean condenser coil. •Check outdoor fan motor; repair/replace as needed. •Check outdoor fan motor wiring; repair/replace as needed. •Check outdoor fan motor capacitor; repair/replace as needed. |
Critical | 2-Stage AC | Pressure error |
03 | Compressor short cycling | •Intermittent
thermostat demand. •Faulty compressor relay. |
•Check
thermostat and thermostat wiring; repair/replace as needed. •Check compressor relay operation; replace as needed. |
minor | 2-Stage AC | System error | |
04 | Locked rotor | •Compressor
bearings are seized. •Failed compressor run capacitor. •Faulty run capacitor wiring. •Low line voltage. |
•Check
compressor operation; repair/replace as needed. •Check run capacitor; replace as needed. •Check wiring; repair/replace as needed. •Verify line voltage is within range on rating plate; contact local utility if out of range. |
Critical | 2-Stage AC | System error | |
05 | Open circuit | •Power
is disconnected. •Failed compressor protector. •Compressor not properly wired to control. |
•Check
circuit breaker and fuses. •Check wiring to unit; repair/replace as needed. •Check compressor; repair/replace as needed. •Check compressor wiring; repair/replace as needed. |
Critical | 2-Stage AC | System error | |
06 | Open start circuit | •Compressor
start winding is open. •Failed compressor run capacitor. •Faulty run capacitor wiring. •Compressor not properly wired to control. •Faulty compressor wiring. |
•Check
compressor; repair/replace as needed. •Check run capacitor; replace as needed. •Check wiring; repair/replace as needed. |
minor | 2-Stage AC | System error | |
06 | Open start circuit lockout | •Compressor
start winding is open. •Failed compressor run capacitor. •Faulty run capacitor wiring. •Compressor not properly wired to control. •Faulty compressor wiring. |
•Check
compressor; repair/replace as needed. •Check run capacitor; replace as needed. •Check wiring; repair/replace as needed. |
Critical | 2-Stage AC | System error | |
07 | OPEN RUN LOCK | Open run circuit | •Compressor
run winding is open. •Compressor not properly wired to control. •Faulty compressor wiring. |
•Check
compressor; repair/replace as needed. •Check wiring; repair/replace as needed. |
minor | 2-Stage AC | System error |
07 | Open run circuit lockout | •Compressor
run winding is open. •Compressor not properly wired to control. •Faulty compressor wiring. |
•Check
compressor; repair/replace as needed. •Check wiring; repair/replace as needed. |
Critical | 2-Stage AC | ||
08 | HIGH LINE VOLT | Low line voltage | •Low line voltage. | •Check
circuit breakers and fuses; Replace if needed. •Verify unit is connected to power supply as specified on rating plate. •Correct low line voltage condition; contact local utility if needed. |
minor | 2-Stage AC | System error |
08 | HIGH LINE VOLT | High/No power supply voltage condition | •High line voltage. | •Correct
high line voltage condition; contact local utility if needed. •Verify unit is connected to power supply as specified on rating place. |
Critical | 2-Stage AC | System error |
09 | LOW SECOND VOLT | Low polit voltage | •Control
detects secondary voltage less than 18 VAC. •Transformer overloaded. •Low line voltage. |
•Check
fuse. •Correct low secondary voltage condition. •Check transformer; replace if needed. |
minor | 2-Stage AC | System error |
A2 | Outdoor air temperature sensor fault | •Shorted
sensor. •Open sensor. •Sensor disconnected. •Sensor out of range. |
•Check
sensor connection. •Replace open/shorted sensor. |
Critical | 2-Stage AC | Sensor error | |
A3 | Outdoor coil temperature sensor fault | •Shorted
sensor. •Open sensor. •Sensor disconnected. •Sensor out of range. |
•Check
sensor connection. •Replace open/shorted sensor. |
Critical | 2-Stage AC | Sensor error | |
b0 | NO ID AIRFLOW | Blower motor not running | •Indoor
blower motor problem. •Communications error between indoor and outdoor unit. |
•Check
indoor fan motor wiring and connectors; Repair/replace if needed. •Check indoor fan motor; Replace if needed. |
Critical | 2-Stage AC | Fan Failure error |
b9 | LOW ID AIRFLOW | Low indoor airflow | •Failed
indoor blower motor. •Indoor /outdoor unit mis-match. •Blocked filters. •Restrictive/undersized ductwork. |
•Check
indoor fan motor wiring and connectors; Repair/replace if needed. •Check indoor fan motor; Replace if needed. •Check ductwork;resize if needed. •Check filters. |
minor | 2-Stage AC | Fan Failure error |
d0[1] | NO NET DATA | Data not yet on network | •Air conditioner/heat pump is wired as part of a communicating system and integrated control module does not contain any shared data. | •Verify
system type (communication or legacy). •Replace control board if necessary. •Rewrite shared data using memory card. •Wire system as a legacy system. |
Critical | 2-Stage AC | System error |
d1[2] | INVALID DATA | Invalid data on network | •Air conditioner is wired as part of a communicating system and integrated control module contains invalid shared data or network data is invalid for the integrated control module | •Verify
system type (communication or legacy). •Replace control board if necessary. •Rewrite shared data using memory card. •Wire system as a legacy system. |
Critical | 2-Stage AC | System error |
d2[3] | SYSTEM MISMATCH | System Mis-match | •Air
conditioner/heat pump is wired as part of a communicating system and outdoor
unit requires airflow greater than indoor unit's airflow capability •Shared data is incompatible with the system or missing parameters |
•Verify
system type (communicating or legacy) •Verify shared data is correct for your specific model; repopulate data if required •Wire system as legacy |
Critical | 2-Stage AC | System error |
d3[4] | INVALID CONFIG | Configuration Mis-match | •Shared data sent to integrated control module does not match hardware configuration | •Verify
shared data is correct for your specific model; Repopulate data if
required. •Verify system type (communicating or legacy). •Wire system as a legacy system. |
Critical | 2-Stage AC | Communication error |
d4[5] | INVALID MC DATA | Invalid memory card data | •Shared data on memory card has been rejected | •Verify
system type (communicating or legacy). •Verify shared data is correct for your specific model; Repopulate data if required. •Verify system type (communicating or legacy). •Wire system as a legacy system. |
Critical | 2-Stage AC | Communication error |
E5 | Blown fuse | •Short in low voltage wiring | •Locate and correct short in low voltage wiring. | Critical | 2-Stage AC | System error | |
EE | Compressor relay contacts are welded shut. | •Compressor relay contacts welded | •Replace control | Critical | 2-Stage AC | System error |