Climate Talk Fault Code Transmitted message Dealer error message Possible Causes Corrective Actions Alarm Status Unit Type Consumer error message
               
               
01 LOW SIDE FAULT Low side fault •Low refrigerant charge.
•Restriction in liquid line.
•Indoor blower motor failure.
•Indoor thermostat set extremely low.
•Verify refrigerant charge; adjust as needed.
•Check for restricted liquid line; repair/replace as needed.
•Check indoor blower motor; repair/replace as needed.
•Check indoor thermostat setting.
minor 2-Stage AC Pressure error
01 LPS LOCKOUT Low pressure cut out trip/lockout(3 trips) •Low refrigerant charge.
•Restriction in liquid line.
•Indoor blower motor failure.
•Indoor thermostat set extremely low.
•Verify refrigerant charge; adjust as needed.
•Check for restricted liquid line; repair/replace as needed.
•Check indoor blower motor; repair/replace as needed.
•Check low pressure switch; repair/replace as needed.
•Check indoor thermostat setting.
Critical 2-Stage AC Pressure error
02 HPS OPEN High side fault •Blocked condenser coil.
•Outdoor fan not running.
•Check and clean condenser coil.
•Check outdoor fan motor; repair/replace as needed.
•Check outdoor fan motor wiring; repair/replace as needed.
•Check outdoor fan motor capacitor; repair/replace as needed.
minor 2-Stage AC Pressure error
02 HPS LOCKOUT High pressure cut out/lockout(3 trips) •Blocked condenser coil.
•Outdoor fan not running.
•Check and clean condenser coil.
•Check outdoor fan motor; repair/replace as needed.
•Check outdoor fan motor wiring; repair/replace as needed.
•Check outdoor fan motor capacitor; repair/replace as needed.
Critical 2-Stage AC Pressure error
03   Compressor short cycling •Intermittent thermostat demand.
•Faulty compressor relay.
•Check thermostat and thermostat wiring; repair/replace as needed.
•Check compressor relay operation; replace as needed.
minor 2-Stage AC System error
04   Locked rotor •Compressor bearings are seized.
•Failed compressor run capacitor.
•Faulty run capacitor wiring.
•Low line voltage.
•Check compressor operation; repair/replace as needed.
•Check run capacitor; replace as needed.
•Check wiring; repair/replace as needed.
•Verify line voltage is within range on rating plate; contact local utility if out of range.
Critical 2-Stage AC System error
05   Open circuit •Power is disconnected.
•Failed compressor protector.
•Compressor not properly wired to control.
•Check circuit breaker and fuses.
•Check wiring to unit; repair/replace as needed.
•Check compressor; repair/replace as needed.
•Check compressor wiring; repair/replace as needed.
Critical 2-Stage AC System error
06   Open start circuit •Compressor start winding is open.
•Failed compressor run capacitor.
•Faulty run capacitor wiring.
•Compressor not properly wired to control.
•Faulty compressor wiring.
•Check compressor; repair/replace as needed.
•Check run capacitor; replace as needed.
•Check wiring; repair/replace as needed.
minor 2-Stage AC System error
06   Open start circuit lockout •Compressor start winding is open.
•Failed compressor run capacitor.
•Faulty run capacitor wiring.
•Compressor not properly wired to control.
•Faulty compressor wiring.
•Check compressor; repair/replace as needed.
•Check run capacitor; replace as needed.
•Check wiring; repair/replace as needed.
Critical 2-Stage AC System error
07 OPEN RUN LOCK Open run circuit •Compressor run winding is open.
•Compressor not properly wired to control.
•Faulty compressor wiring.
•Check compressor; repair/replace as needed.
•Check wiring; repair/replace as needed.
minor 2-Stage AC System error
07   Open run circuit lockout •Compressor run winding is open.
•Compressor not properly wired to control.
•Faulty compressor wiring.
•Check compressor; repair/replace as needed.
•Check wiring; repair/replace as needed.
Critical 2-Stage AC  
08 HIGH LINE VOLT Low line voltage •Low line voltage. •Check circuit breakers and fuses; Replace if needed.
•Verify unit is connected to power supply as specified on rating plate.
•Correct low line voltage condition; contact local utility if needed.
minor 2-Stage AC System error
08 HIGH LINE VOLT High/No power supply voltage condition •High line voltage. •Correct high line voltage condition; contact local utility if needed.
•Verify unit is connected to power supply as specified on rating place.
Critical 2-Stage AC System error
09 LOW SECOND VOLT Low polit voltage •Control detects secondary voltage less than 18 VAC.
•Transformer overloaded.
•Low line voltage.
•Check fuse.
•Correct low secondary voltage condition.
•Check transformer; replace if needed.
minor 2-Stage AC System error
A2   Outdoor air temperature sensor fault •Shorted sensor.
•Open sensor.
•Sensor disconnected.
•Sensor out of range.
•Check sensor connection.
•Replace open/shorted sensor.
Critical 2-Stage AC Sensor error
A3   Outdoor coil temperature sensor fault •Shorted sensor.
•Open sensor.
•Sensor disconnected.
•Sensor out of range.
•Check sensor connection.
•Replace open/shorted sensor.
Critical 2-Stage AC Sensor error
b0 NO ID AIRFLOW Blower motor not running  •Indoor blower motor problem.
•Communications error between indoor and outdoor unit.
•Check indoor fan motor wiring and connectors; Repair/replace if needed.
•Check indoor fan motor; Replace if needed.
Critical 2-Stage AC Fan Failure error
b9 LOW ID AIRFLOW Low indoor airflow •Failed indoor blower motor.
•Indoor /outdoor unit mis-match.
•Blocked filters.
•Restrictive/undersized ductwork.
•Check indoor fan motor wiring and connectors; Repair/replace if needed.
•Check indoor fan motor; Replace if needed.
•Check ductwork;resize if needed.
•Check filters.
minor 2-Stage AC Fan Failure error
d0[1] NO NET DATA Data not yet on network •Air conditioner/heat pump is wired as part of a communicating system and integrated control module does not contain any shared data. •Verify system type (communication or legacy).
•Replace control board if necessary.
•Rewrite shared data using memory card.
•Wire system as a legacy system.
Critical 2-Stage AC System error
d1[2] INVALID DATA Invalid data on network •Air conditioner is wired as part of a communicating system and integrated control module contains invalid shared data or network data is invalid for the integrated control module •Verify system type (communication or legacy).
•Replace control board if necessary.
•Rewrite shared data using memory card.
•Wire system as a legacy system.
Critical 2-Stage AC System error
d2[3] SYSTEM MISMATCH System Mis-match •Air conditioner/heat pump is wired as part of a communicating system and outdoor unit requires airflow greater than indoor unit's airflow capability
•Shared data is incompatible with the system or missing parameters
•Verify system type (communicating or legacy)
•Verify shared data is correct for your specific model; repopulate data if required
•Wire system as legacy
Critical 2-Stage AC System error
d3[4] INVALID CONFIG Configuration Mis-match •Shared data sent to integrated control module does not match hardware configuration •Verify shared data is correct for your specific model; Repopulate data if required.
•Verify system type (communicating or legacy).
•Wire system as a legacy system.
Critical 2-Stage AC Communication error
d4[5] INVALID MC DATA Invalid memory card data •Shared data on memory card has been rejected •Verify system type (communicating or legacy).
•Verify shared data is correct for your specific model; Repopulate data if required.
•Verify system type (communicating or legacy).
•Wire system as a legacy system.
Critical 2-Stage AC Communication error
E5   Blown fuse  •Short in low voltage wiring •Locate and correct short in low voltage wiring. Critical 2-Stage AC System error
EE   Compressor relay contacts are welded shut.   •Compressor relay contacts welded •Replace control Critical 2-Stage AC System error

[1]
Roff, Jeff D.:
Control board does not have the necessary data needed to perform its functions
[2]
Roff, Jeff D.:
Control board does not have the appropriate data needed to perform its functions
[3]
Roff, Jeff D.:
the airflow requirement is greater than the airflow capability of the indoor subsystem
[4]
Roff, Jeff D.:
There is a mismatch between the shared data and the control physical hardware
[5]
Roff, Jeff D.:
The memory card data has been rejected