Climate Talk Fault Code Transmitted message Dealer error message Possible Causes Corrective Actions Alarm Status Unit Type Consumer error message Notes
               
               
b0 MOTOR NOT RUN Blower motor not running •Loose wiring connection at circulator motor power leads or circulator power leads disconnected.
•Open circuit in inductor or loose wiring connection at inductor(3/4 Hp & 1 Hp models only).
•Failed circulator blower motor.
•Tighten or correct wiring connection
•Verify continuous circuit through inductor.  Replace if open or short circuit.
•Check circulator blower motor.  Replace if necessary.
Critical furnace Fan Failure
b1 MOTOR COMM Blower communication error •Loose wiring connection at circulator motor control leads.
•Failed circulator blower motor.
•Failed integrated control module.
•Tighten or correct wiring connection.
•Check circulator blower motor.  Replace if necessary.
•Check circulator integrated control module.  Replace if necessary
Critical furnace Communication Error
b2 MOTOR MISMATCH Blower motor HP mismatch •Incorrect circulator blower motor in furnace.
•Incorrect shared data set in integrated control module.
•Verify circulator blower if motor horse power is the same specified for the specific furnace model.  Replace if necessary.
•Verify shared data set is correct for the specific model.  Re-populate data using correct memory card if required.
Critical furnace Fan Failure
b3 MOTOR LIMITS Blower motor is operating in a power, temperature, or speed limiting condition •Blocked filters.
•Restrictive ductwork.
•Undersized ductwork.
•High ambient temperatures.
•Check filters for blockage.  Clean filters or remove obstructions.
•Check ductwork for blockage.  Remove obstruction.  Verify all registers are fully open.
•Verify ductwork is appropriately sized for system.  Resize/replace ductwork if necessary.
•See "III. Product Description" and "IV. Location Requirements & Considerations" furnace installation requirements.
Critical furnace Fan Failure
b3 MOTOR LIMITS Blower motor is operating in a power, temperature, or speed limiting condition •Blocked filters.
•Restrictive ductwork.
•Undersized ductwork.
•High ambient temperatures.
•Check filters for blockage.  Clean filters or remove obstructions.
•Check ductwork for blockage.  Remove obstruction.  Verify all registers are fully open.
•Verify ductwork is appropriately sized for system.  Resize/replace ductwork if necessary.
•See "Product description" and "Location Requirements & Considerations" for furnace installation requirements.
minor furnace Fan Failure
b4 MOTOR TRIPS Blower motor current trip or lost rotor position •Abnormal  motor loading, sudden change in speed or torque, sudden blockage of furnace air inlet or outlet.  •Check filters, filter grills/registers, duct system, and furnace air inlet/outlet for blockages. Critical furnace Fan Failure
b5 MTR LCKD ROTOR Blower motor locked rotor •Obstruction in circulator blowing housing
•Seized circular blower motor bearings
•Failed circular blower motor
•Check circulator blower for obstructions.  Remove and repair/replace wheel/motor if necessary. 
•Check circular blower motor shaft rotation and motor.  Replace motor if necessary.
Critical furnace Fan Failure
b6 MOTOR VOLTS Voltage or temperature trip •High AC line voltage to furnace
•Low AC line voltage to furnace
•High ambient temperatures
•Check power to furnace.  Verify line voltage to furnace is within the range specified on the furnace rating plate.
•See"III. Product Description" and "IV. Location Requirements & Considerations" furnace installation requirements.
Critical furnace System error
b7 MOTOR PARAMS Incomplete parameters sent to motor •Error with integrated control module
•Motor has a locked rotor condition
•Check integrated control module.  Verify control is populated with correct shared data set.  See data errors above for details.
•Check for locked rotor condition (see error code above for details).
Critical furnace System error
b9 LOW ID AIRFLOW Low indoor airflow •Blocked filters
•Restrictive ductwork
•Undersized ductwork
•Check filter for blockage.  Clean filters or remove obstructions.
•Check ductwork for blockage.  Remove obstructions.  Verify all registers are fully open.
•Verity ductwork is appropriately sized for system.  Resize/replace ductwork if necessary
minor furnace Fan Failure error
bf   Inducer Communication Alarm     Critical furnace System error
c0   Unit Missing     Critical furnace System error
c1   ClimateTalk Network Communication Alarm     Critical furnace System error
c2   Unrecognized Command     Critical furnace System error
c3   Unrecognized Data ID     Critical furnace System error
c4   Invalid DataAC Downloaded Shared Data     Critical furnace System error
c5   Invalid Downloaded Firmware     Critical furnace System error
d0 NO NET DATA Data not yet on network •Furnace does not contain any shared data •Populate shared data set using memory card Critical furnace System error
d1 INVALID DATA invalid data on network •Air conditioner is wired as part of a communicating system and integrated control module does contain any shared data •Replace control board if necessary Critical furnace System error
d2   Invalid system combination     Critical furnace System error          
d4 INVALID MC DATA Invalid memory card data •Shared data set on memory card has been rejected by integrated control module •Verify shared data set is correct for the specific model.  Re-populate data using correct memory card is required. Critical furnace System error
d5   No Cooling Unit Installed     minor furnace System error
d6   No De-Humidifier Installed     minor furnace System error
d7   Wrong Legacy T-Stat Setup Alarm     minor furnace System error
E0 LOCKOUT Lockout due to excessive ignition attempts •Failure to establish flame.  Cause may be no gas to burners, front cover pressure switch stuck open, bad igniter or igniter alignment, improper orifices, or coated/oxidized or improperly connected flame sensor.
•Loss of flame after establishment.  Cause may be interrupted gas supply, lazy burner flames (improper gas pressure or restriction in fuel and/or combustion air piping), front cover pressure switch opening, or improper induced draft blower performance.
•Locate and correct gas interruption.
•Check front cover pressure switch operation (hose, wiring, contact operation).  Correct if necessary.
•Replace or realign igniter.
•Check flame sensor signal.  Clean sensor if coated and/or oxidized.
•Check fuel piping for blockage, proper length, elbows, and termination.
•Verify proper induced draft blower performance.
Critical furnace Safety error
E1 PS1 CLOSED Low stage pressure switch closed at start of heating •Low stage pressure switch contacts sticking.
•Shorts in pressure switch circuit wiring.
•Preplace low stage pressure switch.
•Repair short in wiring.
Critical furnace Pressure error
E2 PS1 OPEN Low stage pressure switch open during heating •Pressure switch hose blocked, pinched, or connected improperly.
•Blocked flue and/or inlet air pipe, blocked drain system or weak induced draft blower.
•Incorrect pressure switch set point or malfunctioning switch contacts.
•Loose or improperly connected wiring.
•Inspect pressure switch hose.  Repair/replace if necessary.
•Inspect flue and/or inlet air piping for blockage, proper length, elbows, and termination.  Check drain system.  Correct as necessary.
•Correct pressure switch set point or contact motion.
•Tighten or correct wiring connection.
Critical furnace Pressure error
E3 HIGH LIMIT OPEN Open high limit switch •Insufficient conditioned air over the heat exchanger.  Blocked filters, restrictive ductwork, improper circulator blower speed, or failed circulator blower motor.
•Flame rollout.
•Misaligned burners, blocked fuel and/or air inlet pipe, or failed induced draft blower.
•Loose or improperly connected wiring.
•Check filters and ductwork for blockage.  Clean filters or remove obstruction.
•Check circulator blower speed and performance.  Correct speed or replace blower motor if necessary.
•Check burners for proper alignment.
•Check fuel and air inlet piping for blockage, proper length, elbows, and termination.  Correct if necessary.
•Check induced draft blower for proper performance.  Replace if necessary.
•Tighten or correct wiring connection. 
Critical furnace Safety error
E4 INPROPER FLAME Flame detected when no flame should be present •Short to ground in flame sensor circuit.
•Lingering burner flame.
•Slow closing gas valve.
•Correct short at flame sensor or in flame sensor wiring.
•Check for lingering flame.
•Verify proper operation of gas valve.
Critical   Safety error
E5 BLOWN FUSE Blown fuse on PCB •Short in low voltage wiring. •Locate and correct short in low voltage wiring. Critical   System error
E6 WEAK FLAME Low flame signal •Flame sensor is coated/oxidized.
•Flame sensor incorrectly positioned in burner flame.
•Lazy burner flame due to improper gas pressure or combustion sir.
•Clean flame sensor if coated/oxidized.
•Check inlet air piping for blockage, proper length, elbows. And termination.
•Compare current gas pressure to rating plate.  Adjust if needed.
•Inspect for proper sensor alignment.
Critical   System error
E7 IGNITER FAULT Igniter fault or improper grounding •Improperly connected igniter.
•Shorted igniter.
•Poor unit ground.
•Igniter relay fault on integrated control module.
•Check and connect wiring from integrated control module to igniter.
•Replace shorted igniter.
•Check & correct unit ground wiring.
•Check igniter output from control.  Replace if necessary.
Critical   System error
E8 PS2 CLOSED  High stage pressure switch stuck closed •High stage pressure switch contacts sticking.
•Shorts in pressure switch circuit wiring.
•Replace high stage pressure switch.
•Repair short in wiring.
Critical   Pressure error
E9 PS2 OPEN High stage pressure switch stuck open •Pressure switch hose blocked, pinched, or connected improperly.
•Blocked flue and/or inlet air pipe, blocked drain system or weak induced draft blower.
•Incorrect pressure switch set point or malfunctioning switch contacts.
•Loose or improperly connected wiring.
•Inspect pressure switch hose.  Repair/replace if necessary.
•Inspect flue and/or inlet air piping for blockage, proper length, elbows, and termination.  Check drain system.  Correct as necessary.
•Correct pressure switch set point or contact motion.
•Tighten or correct wiring connection.
Critical   Pressure error
EA REVERSED PLTY Reversed 115VAC polarity •Polarity of 115 volt AC power to furnace or integrated module is reversed.
•Poor unit ground.
•Review wiring diagram to correct polarity.
•Verify proper ground.  Correct if necessary.
•Check and correct wiring.
Critical   Safety error
EB   Internal Gas Valve Error     Critical   System error
EC   External Gas Valve Error      Critical   System error ULN furnace only, keyed off of “ctIFCNoofGasHeatStages”  = '1';
EC INDUCER FAULT Inducer motor current fault •Lingering Inducer motor overcurrent detected. •Reset system power and verify inducer is running properly.
•Replace inducer or integrated control module, if necessary.
Critical   Safety error Other furnaces, keyed off of “ctIFCNoofGasHeatStages”  > '1';  This will change in the future when other Comforbridge furnace boards are rolled into the Daikin line.  
Ed ROLLOUT OPEN Flame rollout switch is open •Orifice plate out of position.
•Blocked heat exchanger.
•Burners out of alignment.
•Defective heat exchanger.
•Line up orifice plate.
•Remove blockage from heat exchanger.
•Line up burners.
•Check for flame disturbance on roll out when burner comes on.
Critical   Safety error
EE   Internal Control Fault      Critical   System error
EF AUX ALARM FAULT Auxiliary input open •High water level in the evaporation coil. •Check overflow pan and service. Critical   System error
10   Grounding Error      Critical   System error
11   Rollout Switch Open     Critical   System error
12   Redundant Relay Open Alarm     Critical   System error
13   Redundant Relay Stuck Close Alarm     Critical   System error
14   Read or Write to External Flash Fails     Critical   System error
15   RAT Sensor Open     minor   Sensor error
16   RAT Sensor Short     minor   Sensor error
17   SAT Sensor Open     minor   Sensor error
18   SAT Sensor Short     minor   Sensor error
19   Board Temperature Sensor Open     minor   System error
1A   Board Temperature Sensor Short     minor   System error
1B   APS Refence Error      Critical   System error
1C   APS Null Error      Critical   System error
1D   APS Span Error      Critical   System error
1E   APS Pressure Error      Critical   System error
1F   APS Input Error      Critical   System error
76   Equipment communication loss     Critical   Communication Error
77   Thermostat communication loss     Critical   Communication Error
78   Need to connect outdoor unit     Critical   System Error